CFL vertical pump does not water failure causes and solutions:

1, import and export valves are not open, out of the pipeline blockage, runner blockage. ★ check, remove the blockage.

2, the motor is running in the wrong direction, the motor phase loss, the number of revolutions is very slow. ★ adjust the motor direction, tighten the motor wiring.

3, suction tube leakage. ★ tighten the sealing surface, remove the air.

4, the pump is not filled with liquid, the pump cavity with air. ★ Open the pump cover or open the exhaust valve, exhaust air.

5, imported water supply, suction is high, the valve leakage. ★ stop, check, adjust (grid connection and suction with the use of easy to appear)

6, pipe resistance is too large, improper pump selection. ★ reduce the pipe bend, re-select the pump.